CO Combustor unit

De Jong Combustion has delivered one (1) CO-Combustor unit, complete with supplementary fuel gas burners, fuel trains and burner management system.
DESIGN BASIS for CO COMBUSTOR
Flue gas flow : 548.200 Nm3/hr
Flue gas inlet temperature : 739 °C
Max CO content at inlet : 5,31 vol-%
Minimum Oxygen content at outlet :2 vol-%

Complete with
Refractory lining
Inlet for Flue Gas
Inlets for primary combustion air
Inlet for secondary air
3 Register burners c/w igniter & scanners
Optimum air & CO gas distribution for complete conversion of CO into CO2.
KEY DESIGN DATA
Diameter : 8,5 m
Overall length : 17,500 m
Weight : 175 tonn
Burner capacity : 3 x 64 MW
Furnace temperature : 982 °C
Max Fuel gas consumption : 19.500 Nm3/hr
Max air flow : 470.000 Nm3/hr
EMISSION GUARANTEES
The emission at the Combustor outlet will not exceed:
CO : 120 ppmV, ref. 3% O2 dry basis
NOx : 350 mg/nm3, ref. 3% O2 dry basis
Note: The NOx emissions are applicable for RFG mode based without considering the NOx content in the RFG.
Burner data | |
Name | ARAK |